"FL" EXTRUDED ALUMINUM FLANGED WALL VENTS

Specifier Note:  The purpose of this guide specification is to assist the specifier in correctly specifying brick and foundation wall vent products and their installation.  The specifier needs to edit the guide specifications to fit the needs of specific projects.  Contact a Sunvent Industries Product Representative to assist in appropriate product selections.  Throughout the guide specification, there are Specifier Notes to assist in the editing of the file.

 

References have been made within the text of the specification to current MasterFormat section numbers and titles, specifier needs to coordinate these numbers and titles with sections included for the specific project.  Brackets [ ] have been used to indicate when a selection is required.

 

SECTION 08 95 16

WALL VENTS

Sunvent Industries

FL Series Extruded Aluminum Wall Vents

PART 1 - GENERAL

1.1                   SECTION INCLUDES

  1. [Custom] [Standard] size extruded aluminum wall vents with fixed louvers for installation in [masonry] [concrete] [framed] [insert wall description] walls for ventilation.
  2. Accessories:  Insect screens, [damper,] [adjustable damper,] [duct extension,] [and] [inside register].

1.2                   REFERENCES

  1. American Architectural Manufacturers Association (AAMA)
  2. AAMA 605.2 - Voluntary Specification for High Performance Organic Coatings on Architectural Extrusions and Panels.
  3. AAMA 606.1 - Voluntary Guide Specification and Inspection Methods for Integral Color Anodic Finishes for Architectural Aluminum.
  4. AAMA 607.1 - Voluntary Guide Specification and Inspection Methods for Clear Anodic Finishes for Architectural Aluminum.
  5. ASTM International
  6. ASTM B209 - Aluminum and Aluminum-Alloy Sheet and Plate.
  7. ASTM B221 - Aluminum-Alloy Extruded Bar, Rod, Wire, Shape, and Tube.
  8. International Residential Code (IRC): Current edition.
  9. International Building Code (IBC):  Current edition.

1.3                   SUBMITTALS

(Specifier Note: DELETE Submittal Procedures paragraph when not required. Coordinate requirements with Division 01, Section 01 33 00 – Submittal Procedures.)

  1. Refer to Section [01 33 00 Submittal Procedures] [insert section number and title].
  2. Product Data: Submit manufacturer current technical literature for each type of product.
  3. Shop Drawings: Submit detailed drawings showing vent construction, dimensions, and installation details.
  4. Samples: Provide minimum 3 x 5 inch of each color indicated. 

(Specifier Note:  DELETE LEED submittal requirements when project is not pursuing LEED certification.  LEED-NC v2.2 credits are in red LEED-NC v3 credits are in red bold.)

  1. LEED Submittals:
  2. Material and Resources (MR)
  3. Product Certificates for Credit [MR 4] [MR 4.1[and Credit MR 4.2]]: For products having recycled content, documentation indicating percentages by weight of postconsumer and preconsumer recycled content.
  4. Product Certificates for Credit [MR 5] [MR 5.1[and Credit MR 5.2]]:  For products and materials required to comply with requirements for regionally manufactured materials.  Include statement indicating cost, location of manufacturer, and distance to Project for each regionally manufactured material.

PART 2 - PRODUCTS

(Specifier Note: If wall vents are to be included in a Division 3 – Concrete, Division 4 – Masonry or Division 07 – Thermal and Moisture Protection section copy “Wall Vents” article into appropriate Section and delete “Substitution Limitations” and “Materials” paragraphs, edit remaining paragraphs for project conditions.)

2.1                   WALL VENTS

  1. Manufacturer:  Sunvent Industries, a division of Sylro Sales Corporation, 1 Industrial Drive, No. 26, Pelham, New Hampshire 03076; 800-325-4115; www.sunventindustries.com.
  2. Model:  FL Series Extruded Aluminum Wall Vent.

(Specifier Note: DELETE or COORDINATE Substitution Limitations paragraph if substitutions are addressed in Division 01, Section 01 21 00 – Substitution Procedures.)

  1. Substitution Limitations:
  2. Submit written request for approval of substitutions to the Architect [a minimum of [14] days prior to the date for receipt of bids] [Insert time period]. 
  3. Substitutions following award of contract are not allowed except as stipulated in Division 01 – General Requirements.
  4. Materials:
  5. Extruded aluminum:  0.125 inch minimum thickness extruded aluminum complying with ASTM B221, Alloy 6063, Temper T-5.
  6. Sheet aluminum:  0.040 inch minimum thickness complying with ASTM B209.
  7. Fasteners:  Type, size, and spacing as recommended by vent manufacturer for project conditions. 

(Specifier Note: Include sealant paragraph if vents are to be installed with sealant.)

  1. Sealant and backer rod:  Type as [specified in Section 07 92 00 - Joint Sealants] [Insert section number and title] [recommended by vent manufacturer].

(Specifier Note: Wall vents can be ordered in standard sizes ranging from 8 1/8 inch wide by 2 3/8 high to 48 inches wide by 7 3/4 inch tall.  Refer to Sunvent product literature for available stock sizes.  Custom sizes can be ordered to up to 96 inches in width or height without exposed mullions.  Contact Sunvent Industries for vertical load capacities of extruded aluminum wall vents.)

(Specifier Note: When determining vent size Chapter 12; Section 1203.3 of the IBC or Chapter 4; Section R408 of the IRC requires 1 square foot of free area for every 150 square feet of under floor area with one vent opening located within 3 feet of each corner.  If the ground within the under floor area is covered by a Class 1 vapor retarder the vent requirement may be decreased to 1 square foot of vent area for every 1,500 square feet of under floor area provided that the vents are placed to allow for cross-ventilation of the under floor area.)

Wall Vent Free Area in square feet – Standard Sizes:

 

Vent Height (inches)

Vent Width (inches)

 

2-3/8

4-3/4

7-3/4

11-3/4

15-3/4

8-1/8

0.029 SF

0.080 SF

0.136 SF

0.207 SF

0.279 SF

12-5/8

0.044 SF

0.120 SF

0.204 SF

0.310 SF

0.418 SF

15-5/8

0.056 SF

0.156 SF

0.263 SF

0.400 SF

0.540 SF

16-1/2

0.060 SF

0.196 SF

0.280 SF

0.426 SF

0.575 SF

24

0.088 SF

0.271 SF

0.408 SF

0.620 SF

0.836 SF

32

0.117 SF

0.321 SF

0.543 SF

0.826 SF

1.115 SF

  1. Nominal [standard] [custom] sizes: 
  2. Width:  [8-1/8] [12] [15-5/8] [16-1/2] [24] [32] [48] [Insert required width]  inches.
  3. Height:  [2-3/8] [4-3/4] [7-3/4] [11-3/4][15-3/4] [Insert required height]  inches.
  4. Depth:  1-1/2 inches
  5. Free Area per vent:  [Insert wall vent free area] square feet.
  6. Construction:  Extruded aluminum framed vent with 1 inch front flange and overlapping horizontal louver blades fabricated from extruded aluminum sections.
  7. Louver blades:  Fixed, horizontal blades 1 inch deep at 1 inch centers.  Blade shall be set at 45 degrees.  Top of blade formed with storm drip.
  8. Frame:

1)             Material:  Extruded aluminum.

2)             Exposed frame shall be 1 inch wide on all sides of vent.

3)             Bottom of vent shall have an integral water stop at back of vent frame.

  1. Fabricate vents with mechanical connections such that all fasteners are concealed when vent is installed.
  2. Insect screen:  Aluminum 18 by 14 mesh screen set behind louvers in extruded stop on frame.
  3. [Accessories: 
  4. [Adjustable damper:  Operable spring hinged, flap damper set behind horizontal fixed louver blades.  Damper shall be operable from exterior of vent using stainless steel flat head
  5. [Opposed vertical blade damper:  Opposed vertical blade damper set behind horizontal fixed louver blades, unit shall be operable from exterior of vent with screwdriver. (In this case a straight duct extension is required see note below)]

(Specifier Note: Wall vents can be ordered with duct extensions to accommodate various wall thicknesses.  When opposed vertical blade damper is required, assembly must include a minimum 2 inch duct extension between the wall vent and the damper to accommodate the damper.)

 

  1. [Duct extension:  Straight, rectangular aluminum sheet duct extension fastened to wall vent.  Wall depth as indicated on Drawings.]

(Specifier Note: Wall vents can be ordered with inside registers which are shipped loose and attached to inside wall face or attached to duct extensions.)

  1. [Inside register:  Aluminum register, with individually adjusted multi-blade register.  Size to accommodate wall vent size.]]

(Specifier Note: Optional vent attachment is to field fabricate aluminum strap or angles for securing vents in a concealed attachment method (no exposed fasteners on front flange of vent). Clip angles are not provided by manufacturer and must be provided and fabricated by installer.)

  1. [Clip Angles:  Aluminum strap or angles; ASTM B209.]]
  2. Finish:

(Specifier Note: Choose anodized finish, painted finish, or mill finish.  Clear anodized is the standard finish if no finish is specified.)

  1. [Anodized Finish:  [Clear anodized coating complying with AAMA 607.1 - MM10C22A31.]  [[Medium] [Dark] Bronze anodized coating complying with AAMA 606.1 - MM10C22A44.]]

(Specifier Note: Refer to Sunvent Industries product literature for available colors.)

  1. [Painted Finish: 
  2. [Thermoset polyester enamel.] [Fluoropolymer Kynar colored coating complying with AAMA 605.2.]
  3. Color:  [Insert color choice] [As selected by Architect from manufacturer's standard range] [Custom color as designated by Architect].]
  4. [Mill Finish.]

(Specifier Note: Delete if no adjustable dampers, duct extensions or inside registers are required.)

  1. Insect Screen [,] [Adjustable Damper] [Duct extension] [and] [Inside Register]:  Mill finish.

PART 3 - EXECUTION

3.1                   EXAMINATION

  1. Provide field measurements as required to achieve proper fit of wall vents.

(Specifier Note: Edit paragraph to meet project requirements, delete concrete and framed examination requirements if masonry construction is being used.)

  1. [Concrete formwork] [and] [Framed construction]: 
  2. Verify that block-outs have been provided in foundation wall [formwork] [and] [framing].
  3. Verify that recommended clearances and necessary attachment framing has been provided to allow for installation of wall vent.

3.2                   PREPARATION

  1. Masonry Construction: 
  2. [When vents are to be installed as masonry work progresses verify construction schedule and have wall vents delivered so as to avoid delays.]
  3. [When vents are to be installed after masonry work has been completed verify that masonry has support to span vent opening.]

(Specifier Note: Edit paragraph to meet project requirements, delete existing construction paragraph when vents are being installed into new construction.)

  1. Existing Construction: 
  2. Refer to Section [01 73 00 - Execution] [insert section number and title] with regards to cutting of existing construction.
  3. Cut vent opening in existing construction level, plumb, and square.  Provide manufacturer recommended clearances around vent to allow for vent attachment and finishing.

3.3                   INSTALLATION

  1. General:
  2. Do not install vents that are damaged or scratched. Replace damaged and scratched vents.
  3. Install vents secure, level, and plumb.
  4. After installation is complete seal around perimeter flange of vent with sealant.
  5. Masonry construction: 
  6. Build vents into wall with mortar as part of masonry construction specified in Section [04 20 00 – Unit Masonry] [insert section number and title].
  7. Protect exposed vent surfaces from wet mortar.
  8. Install vents, [and] [duct extensions] in accordance with manufacturer's installation instructions and approved shop drawings.
  9. When vents are wider than 30 inches, set only top and bottom of vent in mortar. At vent sides use sealant and backer rod to allow for expansion and contraction of vent.

(Specifier Note: Include “Masonry construction”, “Concrete foundation walls” or “Framed construction” paragraph if vents are to be installed after wall is constructed and finished.  Delete paragraph if vents are installed as masonry wall is constructed.)

  1. [Masonry construction] [Concrete foundation walls] [and] [Framed construction]:
  2. Install vents, [and] [duct extensions] in accordance with manufacturer's installation instructions and approved shop drawings.

(Specifier Note: Choose from 3 attachment methods for vents, the exposed fastener method is the most common and preferred method of installation.)

  1. [Exposed Fasteners:  Drill two holes, minimum, in front flange of vent, mechanically secure vents to wall substrate.]

(Specifier Note: Clip angle attachment method is used when exposed fasteners on front face of vent are not desired.)

  1. [Clip Angles:  Mechanically secure vents to wall substrate using two clip angles, minimum .  Fabricate wall angles to suit wall thickness and mechanically attach to rear of vent box for concealed attachment.]

(Specifier Note: Ductwork attachment is used when vent is being used as an air intake or exhaust vent associated with mechanical ductwork.)

  1. [Ductwork attachment:  Mechanically secure vents to ductwork.]
  2. Attach inside registers to [duct extensions] [inside face of wall] in accordance with manufacturer's installation instructions and approved shop drawings.

3.4                   CLEANING AND PROTECTION

  1. Allow wet mortar or cement plaster on exposed vent surfaces to harden, but not set, prior to removal.  Mortar or cement plaster shall be cleaned from vent with dry burlap rag to prevent scratching.
  2. Remove excess sealant with mineral spirits or other solvent acceptable to sealant manufacturer.
  3. Wash exposed surfaces with solution of mild detergent applied with soft cloth.  Remove dirt from corners.  Wipe surfaces clean.

END OF SECTION